Safe limit of approach distances from overhead power lines for persons and equipment

 
Operating voltage between conductors of overhead power line Safe limit of approach distance for persons and equipment
0 — 750 volts
Insulated or polyethylene
covered conductors (1)
300 millimetres
0 — 750 volts
Bare, uninsulated
1.0 metre
Above 750 volts
Insulated conductors (1) (2)
1.0 metre
750 volts — 40 kilovolts 3.0 metres
69 kilovolts, 72 kilovolts 3.5 metres
138 kilovolts, 144 kilovolts 4.0 metres
230 kilovolts, 260 kilovolts 5.0 metres
500 kilovolts 7.0 metres

Notes: (1) Conductors must be insulated or covered throughout their entire length to comply with this group.